SPECIFICATION

PVC insulated single core solid conductors (P)

Type P

(SRPS N.C3.200)


H07V-U

(HD.21.3.S2)


Rated voltage 450/750V

Test voltage 2500V

 

PRODUCT DESCRIPTION

The conductors consist of a solid copper conductor, insulated with seamless layer of PVC. Constructive-technical data are given in the table below.

INSULATION COLOR

     
   

According to customers wishes

APPLICATION

The condutors are applied during electrical power installations at dry locations, for permanent laying in tubes which may be installed over and under the mortar. Optimal operating temperature of the cable is within the range of -40° C to +70° C. Current electrical load conductor must be adjusted so that the highest temperature must not be less than 70° C.

PACKING

In coils or on reels.

 

Nominal cross section conductor
(mm2)
Insulation thickness
(mm)
Maximal outer diameter
(mm)
Minimal insulation resistance on 70° C
(MOxkm)
Weight
(kg/km)
1,5 0,7 3,3 0,011 19,0
2,5 0,8 3,9 0,010 30,4
4,0 0,8 4,4 0,0085 46,2
6,0 0,8 4,9 0,0070 65,7
10 1,0 6,4 0,0070 109,5
16 1,0 7,4 0,0058 170,4
PDF verzija